Search by Certificate Number

TELE-FONIKA kable S.A.

ul. Hipolita Cegielskiego 1
Myslenice
32400
Poland

Tel: +48 12 652 00 00 • Fax: +48 12 652 51 56
Email: robert.slapak@tfkable.com • Web: www.tfkable.com


Certificate No 814c to BS 6387: 2013, BS EN 50267-2-1: 1999 and IEC 60331-21: 1999


Flame-X 950 SERIES 1

Product

Nominal

csa of

conductor (mm2)

Core

Construction

BS 6387

(See Notes 2, 6 & 7)

EN 50267-2-1

IEC 60331-21

(See Note 8)

LPCB
Ref. No.
Flame-X 950 SERIES 1

1.5

One(1)

C, W, Z(2, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

2.5

One(1)

C, W, Z(2, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

4.0

One(1)

C, W, Z(2, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

6.0

One(1)

C, W, Z(2, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

10

One(1)

C, W, Z(2, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

16

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

25

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

35

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

50

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

70

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

95

One(1)

C, W, Z(3, 4 & 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

120

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

150

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

185

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

240

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

300

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

400

One(1)

C(3, 5)

<0.5%HCl

Complies(6)

814c/01
Flame-X 950 SERIES 1

500

One(1)

-

<0.5%HCl

Complies(6)

814c/01

 

Uo/U 600/1000V

Notes:
1)    Stranded conductor only.
2)    To satisfy the requirement of BS 6387, testing for C, W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic  element.
3)    To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
4)    To satisfy the requirement of BS 6387, testing for W & Z categories were conducted using a 20mm stainless steel conduit as the other metallic element.
5)    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
6)    These cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950oC and at a voltage rating of 600V.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page