Search by Certificate Number

AIR Fire S.p.A.

Via Tenuta della Mistica - 33/37
Rome
00155
Italy

Tel: +34 680395217
Email: info@airfire.eu • Web: www.airfire.eu


Certificate No 1408b to LPS 1666: Issue 1.0


ARMANfire HFC-227ea Direct Low Pressure (DLP) Application Fixed Fire Suppression Systems

Product

Container Size

Description

Detector Tube

Ventilation (Enclosed or Open Vents)

Air Flow (Forced / Natural)

LPCB
Ref. No.
ARF22701TB

1.0 Litre

1 kg HFC-227ea DLP system

P/N: 125101

6mm o/d

Enclosed & open options 4

Natural airflow only

1408b/01
ARF22703TB

3.8 Litre

2 kg HFC-227ea DLP system

P/N: 125101

6mm o/d

Enclosed & open options4

Natural airflow only

1408b/02

 

Notes:
1)   AIR Fire S.p.A., ARMANfire HFC-227ea DLP Systems shall be configured, installed, serviced and maintained in accordance with;                                      
      - Design and Calculations Manual ARMANfire - DCMARF2270XTBEN-A - V1.1 / Date: 31/10/2018
      - Technical User Manual ARMANfire - TUMARF2270XTBEN-A - V1.1 / Date: 18/09/2018
2)   These systems are intended solely to provide enhanced local fire protection.   They are not intended for use as whole room or building fire protection systems.  
3)   The systems use a single method for detection and delivery of the extinguishing agent to the activation point.
     - System operation pressure: 18 bar @ 20°C.
     - System operation temperature range: -20°C to +60°C.
4)   The above systems may have air vents at low and/or high level (refer note 1).

 


 

To read the Red Book section introduction click here.

 