Honeywell Life Safety Systems (Novar Systems Ltd)

140 Waterside Road
Hamilton Industrial Park
Leicester
LE5 1TN
United Kingdom

Tel: +44 (0)116 246 2000 • Fax: +44 (0)116 246 2300
Email: gent_enquiry@gent.co.uk • Web: www.gent.co.uk


Certificate No 524c-(cl-1) to EN 54-20:2006


Aspirating Smoke Detectors

Product Description LPCB
Ref. No.
ALL-SPEC ASD

Notes:

  1. Approval of the detector is conditional upon the following requirements:
  2. For compliance with Clause 5.10 of EN 54-20: 2006, the detector shall be supplied with power from a power supply conforming to the requirements of EN 54-4.
  3. System design, installation and commissioning shall be performed in accordance with the manufacturer's installation guide, associated manuals and design software TF-SC-1 HW.
  4. The detector shall be installed with sampling pipe conforming to EN 61386-1, to at least Class 1131.
  5. 2.        Approved detector configurations (Class A, Class B and Class C):

    • ALL-SPECx (standard version, no bargraph display, 1 alarm, not available for networking)
    • ALL-SPECx-FR (deep freeze version, no bargraph display, 1 alarm, not available for networking )
    • ALL-SPECx-SL (silent version, no bargraph display, 1 alarm, not available for networking)

                  X=detector 1 or 2

    3.        The approved detector must incorporate one or two of the following detector modules:

    • ASD-TP-001-L (standard version, sensitivity of 0.015%/m)
    • ASD -TP-001-L-F (deep freeze version, sensitivity of 0.015%/m)
    • ASD -TP-01-L (standard version, sensitivity of 0.10%/m)
    • ASD -TP-01-L-F (deep freeze version, sensitivity of 0.10%/m)
    • ASD -TP-05-L (standard version, sensitivity of 0.50%/m)
    • ASD -TP-05-L-F (deep freeze version, sensitivity of 0.50%/m)

                  X=detector 1 or 2

524c/01
HI-SPEC ASD

Notes:

  1. Approval of the detector is conditional upon the following requirements:
  2. For compliance with Clause 5.10 of EN 54-20: 2006, the detector shall be supplied with power from a power supply conforming to the requirements of EN 54-4.
  3. System design, installation and commissioning shall be performed in accordance with the manufacturer's installation guide, associated manuals and design software TF-SC-1 HW.
  4. The detector shall be installed with sampling pipe conforming to EN 61386-1, to at least Class 1131.
  5. 2.        Approved detector configurations (Class A, Class B and Class C):

    • HI-SPECx (standard version, bargraph display, 3 alarms, prepared for networking)
    • HI-SPECx-FR (deep freeze version, bargraph display, 3 alarms, prepared for networking)
    • HI-SPECx -SL (silent version, bargraph display, 3 alarms, prepared for networking)

    3.        The approved detector must incorporate one or two of the following detector modules:

    • ASD-TT-001-L (standard version, sensitivity of 0.015%/m)
    • ASD -TT-001-L-F (deep freeze version, sensitivity of 0.015%/m)
    • ASD -TT-01-L (standard version, sensitivity of 0.10%/m)
    • ASD -TT-01-L-F (deep freeze version, sensitivity of 0.10%/m)
    • ASD -TT-05-L (standard version, sensitivity of 0.50%/m)
    • ASD -TT-05-L-F (deep freeze version, sensitivity of 0.50%/m)
524c/03
COMPACT ASD

Notes:

  1. Approval of the detector is conditional upon the following requirements:
  2. For compliance with Clause 5.10 of EN 54-20: 2006, the detector shall be supplied with power from a power supply conforming to the requirements of EN 54-4.
  3. System design, installation and commissioning shall be performed in accordance with the manufacturer's installation guide, associated manuals and design software TF-SC-1 HW.
  4. The detector shall be installed with sampling pipe conforming to EN 61386-1, to at least Class 1131.
  5. 2.        Approved detector configurations, sensitivity of 0.50%/m (Class A, Class B and Class C):

    • ASD-CM (version with 2 stages of alarm)
    • ASD-CM2 (version with 2 stages of alarm, ROOM IDENT)
524c/04

 

 


 