Search by Certificate Number

Kidde Fire Protection

1st Floor Stokenchurch House
Oxford Road
Stokenchurch
High Wycombe
Buckinghamshire
HP14 3SX
United Kingdom

Tel: +44 (0)1494 480410
Email: General.enquiries@kiddeuk.co.uk • Web: www.kfp.co.uk


Certificate No 594e to LPS 1230


Kidde Inert Gas System (400 Series) - IG55

Product

Risk

Design Concentration

Comments

LPCB
Ref. No.
IG-55

Class A Standard

(Solid fires e.g. Paper, wood, plastics)

38.9 %

Design concentration includes 30% safety factor

594e/02
IG-55

Class A Cables  

(Solid fire risks including Cables)

44.2 %

Confirmation that minimum safety factor is adequate

594e/02
IG-55

Class B

(Liquid Fires e.g. heptane)

45.9 %

Design concentration includes 30% safety factor

594e/02

 

Notes:
This system is suitable for storage in environmental conditions from -20°C to +50°C
Storage pressure is specified as 200 bar or 300 bar @ 15°C.  System pressure is specified as 55 bar.

This system uses:
Components as listed in Part 4, Section 2.1 and as described in

Kide Fire Protection Inert Gas System (400 Series) Design, Installation, Operation and Maintenance Manual:  
P/N 06-237518-001, dated July 2018, Revision AA which utilises the following software

Software Programme:   Kidde Fire Protection - Flow Calculation v 4.00,
                                     Licensed to Kidde Fenwal  
                                      Copyright: Jensen Hughes Inc

Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables System test concentration.  Where this value is lower than the Class A Standard value, the Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number P102562-1002.
Extinguishing concentrations are as verified in BRE Test Report Number P102562-1001

 


 