Search by Certificate Number

Kidde Fire Protection

1st Floor Stokenchurch House
Oxford Road
Stokenchurch
High Wycombe
Buckinghamshire
HP14 3SX
United Kingdom

Tel: +44 (0)1494 480410
Email: General.enquiries@kiddeuk.co.uk • Web: www.kfp.co.uk


Certificate No 594d to LPS 1230


Argonite C Series 300 bar Fixed Gaseous Fire Extinguishing System

Product

Risk

Design Concentration

Comments

LPCB
Ref. No.
Argonite C Series

Class A Standard (Solid fires e.g paper, wood, plastics)

40.3%

Design concentration includes 30% safety factor

594d/01
Argonite C Series

Class A Cables (Solid fire risks including cables)

44.0%

Confirmation that minimum safety factor is adequate.

594d/01
Argonite C Series

Class B (Liquid Fires e.g. heptane)

47.5%

Design concentration includes 30% safety factor

594d/01

 

Notes:
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentrations Class A Cables System test concentration - where this is lower than the Class A Standard value, the Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 253355
Extinguishment concentrations are as tested in BRE Test Report Number 206879 & 216485 (ISO 14520-1 tests).
This system uses:
 Design, Installation, Maintenance and User Manual: General Manual - Argonite C60 System, MA -01-9008-0100, Revision 1.0 dated November 2011.
Software Programme: Kidde Argonite Program, VdS-Version 1.7 (2009).
a) This system is suitable for storage in environmental conditions from -20° to +50°.
b) Container pressure is specified as 300 bar @ 15°C.
 

 


 

To read the Red Book section introduction click here.

 

< back to results page