Search by Certificate Number

Bahra Cables Company

CPC Industrial Park
Bahra
Jeddah 21432
Kingdom of Saudi Arabia

Tel: +966 25911115, (Toll Free) 8001248111 • Fax: +966 25915683
Email: fsb@bahra-cables.com • Web: www.bahra-cables.com


Certificate No 1069a to BS 6387: 2013, IEC 60331-21: 1999, BS EN 50267-2-1: 1999, BS EN 50267-2-3: 1999 & BS EN 61034-2: 2005


FSB Wires

Product

Nominal csa of conductor (mm²)

Core construction

BS 6387

BS EN 50267-2-1

BS EN 50267-2-3

BS EN 61034-2

IEC 60331-21

LPCB
Ref. No.
FSB Wires

2.5

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

4.0

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

6.0

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

10

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

16

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

25

One(1)

C, W, Z(2, 3)

<0.5% HCl

Complies

>60%

Complies(5)

1069a/01
FSB Wires

35

One(1)

C, W, Z(2, 3)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

50

One(1)

C, W, Z(2, 3)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

70

One(1)

C, W, Z(2, 3)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

95

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

120

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

150

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

185

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

240

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

300

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

400

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01
FSB Wires

500

One(1)

C(2, 4)

<0.5% HCI

Complies

>60%

Complies(5)

1069a/01

 

Uo/U 450/750V

Notes:
1)    Stranded conductor only.
2)    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
3)    To satisfy the requirement of BS 6387:2013, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit
    as the other metallic element.
4)    To satisfy the requirement of BS 6387:2013, testing for C category was conducted using a 38mm stainless steel conduit as the other
    metallic element.
    5)    The FSB Wires cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950ºC for a duration of
    180mins, at a voltage rating of 450V.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page