Search by Certificate Number

UTC Fire & Security Inc. Trading as Edwards Systems Technology

8985 Town Center Parkway
Bradenton
Florida
34202
USA

Tel: 941-739-4214
Email: sean.hawes@carrier.com • Web: www.ccs.utc.com


Certificate No 262w to EN 54-3: 2001 + A1: 2002 + A2: 2006

Certificate No 262aa to EN 54-3:2001 + A1:2002 + A2:2006 and EN 54-23:2010
Certificate No 262ac to EN 54-23:2010
Certificate No 904f-(cl-1) to EN 54-3:2001 + A1:2002 + A2:2006




Product Description LPCB
Ref. No.
G1x-HD-E

Genesis Temporal Horn        

Notes:

1.   Approved with back boxes G1B-MP and 27193-16

2.   Meets the requirements of EN 54-3 at all volumes and the following tones:-

      Continuous 3200HZ (interrupted at 40Hz)

      Temporal 3200Hz (interrupted at 40Hz); 2 pulses 0.5s on / 0.5s off,

      1 pulse  0.5s on / 1.5s off, repeat.        

3.   x denotes housing colours

      Blank         = White housing

      R        = Red housing

      F        = White housing with Fire Marking

      RF        = Red housing with Fire Marking.

262w/02
G1x-HDVM-E

Genesis Type A Indoor Temporal Sounder / Beacon

Notes:

  1.    Approved with backboxes G1xB-MP and 27193-xx
  2.    Meets the requirements of EN 54-3 at the following tones:-

       Continuous 3200Hz (interrupted at 40Hz)

       Temporal 3200Hz (interrupted at 40Hz); 2 pulses 0.5s on / 0.5s off,

       1 pulse 0.5s on / 1.5s off, repeat

3.   The wall mounted VAD meets the requirements of EN 54-23:2010

     for the following:
       - Category (light pattern details):

      @15cd (W-3.0-2.8 or W-2.5-3.3)

      @30cd (W-4.4-4.5)

      @75cd (W-6.0-7.5)

      @110cd (W-6.5-8.4)

       - Synchronization

         Flash rate 1Hz

4.   x denotes housing colours

      Blank = White housing

       R        = Red housing

       F        = White housing with Fire Marking

       RF      = Red housing with Fire Marking

262aa/01
G1x-VM-E

Genesis Type A Indoor Temporal Beacon

Notes:

  1.    Approved with backboxes G1xB-MP and 27193-xx
  2.    The wall mounted VAD meets the requirements of EN 54-23:2010

       for the following:
       - Category (light pattern details):

       @15cd (W-3.0-2.8 or W-2.5-3.3)

       @30cd (W-4.4-4.5)

       @75cd (W-6.0-7.5)

       @110cd (W-6.5-8.4)

       - Synchronization

       Flash rate 1Hz

3.    x denotes housing colours

       Blank = White housing

       R        = Red housing

       F        = White housing with Fire Marking

       RF      = Red housing with Fire Marking

262ac/01
SIGA-AB4GI

Sounder Base

Notes:

1.   Certified for use with fire detector models - SIGA-IPHSI, SIGA-PHSI, SIGA-PSI, SIGA-IS and SIGA-HRSI.

2.   Meets the requirements of EN 54-3 with steady and temporal tones and operating voltages from 16-33 VDC.

3.   Certified for use with AB4G-SB Surface mounting box.

4.   This is a Type A device.

904f/01

 

Ancillaries
G1B-MP Back box G1 series, white
G1RB-MP Red Back box, G1 Series, plastic
27193-16 Back box, surface white
27193-11 Red back box, Surface, Metal
AB4G-SB Surface Mounting Box


 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page