Certificate No 221c to BS 6387:2013, EN 50200:2006 (Class PH120, BS 8434-2:2003+A2:2009 (120mins), EN 50267-2-1:1999 and IEC 60331-21:1999


Firetec Single Core LSZH

Product

Nominal csa

of conductor (mm2)

Core

Construction

(excluding

drain wire

and earth)

BS 6387

EN 50200

(outer covering)

BS 8434-2

EN 50267-2-1

IEC 60331-21

LPCB
Ref. No.
Firetec Single Core LSZH

1.0

One(1)

C, W, Z(2, 3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

1.5

One(1)

C, W, Z(2, 3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

2.5

One(1)

C, W, Z(2, 3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

4.0

One(1)

C, W, Z(2,3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

6.0

One(1)

C, W, Z(2, 3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

10

One(1)

C, W, Z(2, 3)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

16

One(1)

C, W, Z(2, 4, 5)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

25

One(1)

C, W, Z(2, 4, 5)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8, 9)

8 & 9)

221c/01
Firetec Single Core LSZH

35

One(1)

C, W, Z(2, 4, 5)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

50

One(1)

C( 2, 5)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

70

One(1)

C(2, 5)

PH120(6)

120mm(6)

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

95

One(1)

C(2, 5)

-

-

<0.5%HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

120

One(1)

C(2, 5)

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

1000

One(1)

-

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

150

One(1)

C(2, 5)

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

185

One(1)

C(2, 5)

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

240

One(1)

C(2, 5)

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

300

One(1)

C(2, 5)

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

400

One(1)

-

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

630

One(1)

-

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01
Firetec Single Core LSZH

800

One(1)

-

-

-

<0.5% HCI

90min @ 950oC(8 & 9)

221c/01

 

Uo/U 600/1000V

    Notes:
1.    Stranded conductor only.
2.    BS 6387:2013 does not recognise single core cables.  However, in order to test to the methodologies given in BS 6387:2013 required by specific regions, testing was conducted by inserting cable into stainless steel conduit.
3.    To satisfy the requirement of BS 6387:2013, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element.
4.    To satisfy the requirement of BS 6387:2013, testing for W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element.
5.    To satisfy the requirement of BS 6387:2013, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
6.    Standards EN50200 & BS 8434-2 do not recognise cables in conduit.  However in order to test to the methodologies given in EN 50200 & BS8434-2 required by specific regions, testing was conducted by inserting cable into a 20mm steel conduit.
7.    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
8.    These cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950ºC and at a voltage rating of 600V.
9.    The Firetec Single Core LSZH cable also met IEC 60331-21: 1999 when installed in steel conduit.

 


 

To read the Red Book section introduction click here.

 

< back to results page