Search by Certificate Number

Sterling Safety Systems

Unit B12a, Holly Farm Business Park
Honiley
Warwickshire
CV8 1NP
United Kingdom

Tel: +44(0)1926485282 • Fax: +44(0)1926485090
Email: info@sterlingsafety.co.uk • Web: www.sterlingsafety.co.uk


Certificate No 928y-(cl-2) to EN 54-3:2001 + A1:2002 + A2:2006; EN 54-23:2010
Certificate No 928z-(cl-2) to EN 54-3:2001 + A1:2002 + A2:2006; EN 54-17:2005; EN 54-18:2005; EN 54-23: 2010


Visual & Audible Warning Devices

Product Description LPCB
Ref. No.
HFC-SBR-23-03

Conventional Type A/B (indoor/outdoor) Wall Sounder and Visual Alarm Device (Red Body)

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

2. The wall mounted VAD meets the requirements of EN 54-23 for the following:

- Category W-2.5-7

- Flash rate - 0.5Hz

- Synchronization

928y/01
HFC-SBR-23-03 + HFI-SIM-01

Altair Addressable Type A/B (indoor/outdoor) Wall Sounder and Visual Alarm Device with Short Circuit Isolator (Red Body)

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

2. The wall mounted VAD meets the requirements of EN 54-23 for the following:

- Category W-2.5-7

- Flash rate - 0.5Hz

- Synchronization

3. Device is only addressable when used in conjunction with HFI-SIM-01

928z/01
HFC-SBW-23-03

Conventional Type A/B (indoor/outdoor) Wall Sounder and Visual Alarm Device (White Body)

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

2. The wall mounted VAD meets the requirements of EN 54-23 for the following:

- Category W-2.5-7

- Flash rate - 0.5Hz

- Synchronization

928y/01
HFC-SBW-23-03 + HFI-SIM-01

Altair Addressable Type A/B (indoor/outdoor) Wall Sounder and Visual Alarm Device with Short Circuit Isolator (White Body)

Notes:

1. Meets the requirements of EN 54-3 at the following tone settings:

Tone 1 - Warble Tone 800Hz for 500ms, then 1000Hz for 500ms

Tone 2 - Continuous Tone, 970Hz

Tone 3 - Slow Whoop (Dutch), 500-1200Hz for 3500ms, then off for 500ms

Tone 4 - German DIN Tone, 1200-500Hz swept every 1000ms (1Hz)

2. The wall mounted VAD meets the requirements of EN 54-23 for the following:

- Category W-2.5-7

- Flash rate - 0.5Hz

- Synchronization

3. Device is only addressable when used in conjunction with HFI-SIM-01

928z/01

 

Ancillaries
HFI-SIM-01    Addressable module with short circuit isolator

 


 

To read the Red Book section introduction click here.

 