Certificate No 1199d-(cl-1) to EN 54-20:2006




Product Description LPCB
Ref. No.
Stratos Micra 25

High Sensitivity Aspirating Smoke Detector (Branded as Kidde Airsense)

Notes:

1.   For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2.   The approval of the detector is conditional upon the following requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.31%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/01
Stratos Micra 100

High Sensitivity Aspirating Smoke Detector (Branded as Kidde Airsense)

Notes:

1.   For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2.   The approval of the detector is conditional upon the following requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/02
Stratos HSSD 2

High Sensitivity Aspirating Smoke Detector (Branded as Kidde Airsense)

(Stratos HSSD 2 Stand Alone Command Module Ancillary)

Notes:

1.   For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2.   The approval of the detector is conditional upon the following requirements:

a)   Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b)   The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD

1199d/03
Stratos HSSD 2 + Command Module

High Sensitivity Aspirating Command Module Smoke Detector (Branded as Kidde Airsense)

Notes:

1.   For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2.   The approval of the detector is conditional upon the following requirements:

a)   Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b)   The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/04
Stratos HSSD 2 Minimum Display Module

High Sensitivity Aspirating Minimum Display Version Smoke Detector (Branded as Kidde Airsense) (Stratos HSSD 2 Stand Alone Command Module Ancillary)

Notes:

1.   For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2.   The approval of the detector is conditional upon the following requirements:

a)   Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b)   The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/05
Senator 25

High Sensitivity Aspirating Smoke Detector (Branded as Kidde)

Notes:

1. For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2. The approval of the detector is conditional upon the following

requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.31%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/01
Senator 100

High Sensitivity Aspirating Smoke Detector (Branded as Kidde)

Notes:

1. For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2. The approval of the detector is conditional upon the following

requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/02
Senator 200

High Sensitivity Aspirating Smoke Detector (Branded as Kidde)

(Senator Command Module Ancillary)

Notes:

1. For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2. The approval of the detector is conditional upon the following requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/03
Senator 200 + Command Module

High Sensitivity Aspirating Command Module Smoke Detector (Branded as Kidde)

Notes:

1. For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2. The approval of the detector is conditional upon the following requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/04
Senator 200 Minimum Display Module

High Sensitivity Aspirating Minimum Display Version Smoke Detector (Branded as Kidde ) (Senator Command Module Ancillary)

Notes:

1. For compliance with Clause 5.10 of EN 54-20:2006, the detector shall be supplied with power from a power supply complying with EN 54-4.

2. The approval of the detector is conditional upon the following

requirements:

a) Design, installation and commissioning are performed in accordance with the system design manual and instructions.

b) The device is approved for sensitivity Classes A, B and C for sensitivities up to 0.62%/m, 1.95%/m and 4.65%/m respectively. The Class of any pipe/hole configuration and detector sensitivity must be determined using PipeCAD.

1199d/05
9-30783

Detector Module for Stratos ModuLaser (Branded AirSense)

Incorporating the following ancillary equipment:

-Apollo APIC Card for Stratos ModuLaser (Part No: 9-30430)

Notes:
1. For compliance with EN 54-20:2006, the Detector Module(s) (9-30783) must be used in conjunction with at least one of the following ancillary equipment:

- Command Display Module, (Part No: 9-30782)
- Standard Display Module, (Part No: 9-30781)
- Minimum Display Module, (Part No: 9-30780)


2. For compliance with clause 5.10 of EN 54-20:2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

3. The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeCAD software.

4. The approval of the detector is conditional upon the following requirements:

- Design including accessories used, installation and commissioning are performed in accordance with the system installation manual 4-4001-501-1003.

1199d/07
FHSD8330

LaserSense ModuLaser, Detector Module (Branded Edwards)

Incorporating the following ancillary equipment:

-Apollo APIC Card for Stratos ModuLaser (Part No: 9-30430)

Notes:
1. For compliance with EN 54-20:2006, the Detector Module (FHSD8330) must be used in conjunction with at least one of the following ancillary equipment:

- LaserSense Modulaser, Command Display Module, (Part No: FHSD8320) (Branded Edwards)
- LaserSense Modulaser, Standard Display Module, (Part No: FHSD8310) (Branded Edwards)
- LaserSense Modulaser, Minimum Display Module, (Part No: FHSD8300) (Branded Edwards)


2. For compliance with clause 5.10 of EN 54-20:2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

3. The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeCAD software.

4. The approval of the detector is conditional upon the following requirements:

- Design including accessories used, installation and commissioning are performed in accordance with the system installation manual 04-4001-501-2003-08.

1199d/07
9-30783-KID

Senator ModuLaser, Detector Module (Branded Kidde)

Incorporating the following ancillary equipment:

-Apollo APIC Card for Stratos ModuLaser (Part No: 9-30430)

Notes:
1. For compliance with EN 54-20:2006, the Detector Module (9-30783-KID) must be used in conjunction with at least one of the following ancillary equipment:

- Senator ModuLaser, Command Display Module, (Part No: 9-30782-KID) (Branded Kidde)
- Senator ModuLaser, Standard Display Module, (Part No: 9-30781-KID) (Branded Kidde)
- Senator ModuLaser, Minimum Display Module, (Part No: 9-30780-KID) (Branded Kidde)


2. For compliance with clause 5.10 of EN 54-20:2006, all detectors and displays shall be supplied with power from a power supply conforming with the requirements of EN 54-4.

3. The device is approved for sensitivity Classes A, B and C.  The Class of any pipework and hole configuration, detector sensitivity and equipment parameters must be determined using PipeCAD software.

4. The approval of the detector is conditional upon the following requirements:

- Design including accessories used, installation and commissioning are performed in accordance with the system installation manual 04-4001-501-0003-08.

1199d/07

 

Ancillaries:
Stratos HSSD 2 Stand Alone Command Module (Branded as Kidde Airsense)
Senator Command Module (Branded as Kidde)
FHSD8320 Command Display Module (Branded as Edwards)
FSHD8310 Standard Display Module (Branded as Edwards)
FSHD8300 Minimum Display Module (Branded as Edwards)
9-30782-KID Command Display Module (Branded as Kidde)
9-30781-KID Standard Display Module (Branded as Kidde)
9-30780-KID Minimum Display Module (Branded as Kidde)

 


 