Search by Certificate Number

Huzhou Jiusheng Electric Co Ltd

1000 Xifeng Road
Huzhou Economy & Technology Area
Huzhou
Zhejiang
China

Tel: +86 572 222 8188 • Fax: +86 572 222 8177
Email: zjh@hz-tec • Web: www.teccable.com


Certificate No 948b to EN 60702-1: 2002, BS 6387: 2013 (Category C,W,Z), EN 50200:2006 (Class PH120), BS 8434-2:2003+A2:2009 (120mins), BS 5839-1:2013 (Clause 26.2e & EN 50267-2-1:1999


TEC MI SERVED CABLE (LIGHT DUTY)

Product

Nominal csa

of conductor

(mm²)

Core Construction

EN 60702-1

BS 6387

EN 50200

BS 8434-2

BS 5839-1 Clause 26.2

EN 50267-2-1 (outer covering)

LPCB
Ref. No.
TEC MI SERVED CABLE (LIGHT DUTY)

1.0(1,2)

2, 3, 4 & 7

Complies

C,W,Z

Class PH120

120min

Enhanced(4)

<0.5% HCl

948b/01
TEC MI SERVED CABLE (LIGHT DUTY)

1.5(1,2)

2, 3, 4 & 7

Complies

C,W,Z

Class PH120

120min

Enhanced(4)

<0.5% HCl

948b/01
TEC MI SERVED CABLE (LIGHT DUTY)

2.5(1,2)

2, 3, 4 & 7

Complies

C,W,Z

Class PH120

120min

Enhanced(4)

<0.5% HCl

948b/01
TEC MI SERVED CABLE (LIGHT DUTY)

4.0(1,2)

2

Complies

C,W,Z

Class PH120

120min

Enhanced(4)

<0.5% HCl

948b/01

 

Uo/U 300/500V

Notes:
1.    Solid conductor only.
2.    The above cables are certified in Served construction only.
3.    In meeting the requirements of EN 60702-1: 2002, the TEC MI SERVED CABLE (LIGHT DUTY) listed met the requirements of smoke density of IEC 61034-2: 2005 and also met the requirements of pH & conductivity when tested in accordance with IEC 60754-2: 2011.
4.    The TEC MI SERVED CABLE (LIGHT DUTY) listed conform to EN 60702-1: 2002, met Class PH120 when tested in accordance with EN 50200: 2006 and met a duration of 120min when tested in accordance with BS 8434-2: 2003+A2:2009 and hence met the requirements for an Enhanced fire resistant cable as described in Clause 26.2 of BS 5839-1: 2013.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page