Search by Certificate Number

LEONI Studer AG

Herrenmattstr. 20
CH 4658 Däniken
Switzerland

Tel: +41 62 288 82 82 • Fax: +41 62 288 83 83
Email: sales-export@leoni.com • Web: www.leoni.com


Certificate No 896c to BS 6387: 2013 (CWZ), EN 60754-1:2014, EN 61034-2:2005+A1:2013, IEC 60332-1-2:2004, IEC 60331-21: 1999 and IEC 60332-3-24: 2009


BETAflam FR-MI 110 Cable Multicore, STA & SWA

Product

Nominal csa of

conductor (mm2)

Core Construction

BS 6387

EN 60754-1

EN 61034-2

IEC 60332-1-2

IEC 60331-21

IEC 60332-3-24

LPCB
Ref. No.
BETAflam FR-MI 110 Cable Multicore, STA & SWA

1.5(1)

2 - 41

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

2.5(1)

2 - 24

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

4.0(1)

2 - 7

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

6.0(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

10(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

16(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

25(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

35(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

50(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

70(1)

2 - 5

CWZ

<0.5%HCI

>60%

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

95(1)

2-5

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

120(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

150(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

185(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

240(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

300(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01
BETAflam FR-MI 110 Cable Multicore, STA & SWA

400(1)

3 & 4

CWZ

<0.5%HCI

-

Complies(4)

Complies(3)

Complies

896c/01

 

Uo/U    600/1000V

Notes:
1.    Stranded conductor only.
2.    These cables met category CWZ when tested for voltage rating 600/1000V.
3.    The BETAflam FR-MI 110 Cable Multicore cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950oC and at a voltage rating of 600/1000V.
4.    The flame test IEC 60332-1-2 is fulfilled for the complete cable and for the insulated conductor without sheath.

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page