Search by Certificate Number

LEONI Studer AG

Herrenmattstr. 20
CH 4658 Däniken
Switzerland

Tel: +41 62 288 82 82 • Fax: +41 62 288 83 83
Email: sales-export@leoni.com • Web: www.leoni.com


Certificate No 896b to BS 6387: 1994, BS EN 50267-2-1: 1999, BS EN 61034-2: 2005, IEC 60331-21: 1999 and IEC 60332-3-24: 2000


BETAflam FR-MI 110 Cable Single Core SI

Product

Nominal csa of

conductor (mm2)

Core Construction (see note 1)

BS 6387 (see notes 2-4)

BS EN 50267-2-1

BS EN 61034-2

IEC 60331-21 (see note 9)

IEC 60332-3-24

LPCB
Ref. No.
BETAflam FR-MI 110 Cable Single Core SI

1.5

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

2.5

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

4.0

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

6.0

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

10

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

16

one

C,W,Z(5)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

25

one

C,W,Z(6,7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

35

one

C,W,Z(6,7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

50

one

C,W,Z(6,7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

70

one

C,W,Z(6,7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

95

one

C,W,Z(6,7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

120

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

150

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

185

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

240

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

300

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

400

one

C(7)

<0.5%HCI

>60%

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

500

one

Complies(8)

<0.5%HCI

-

Complies

Complies

896b/01
BETAflam FR-MI 110 Cable Single Core SI

630

one

Complies(8)

<0.5%HCI

-

Complies

Complies

896b/01

 

Uo/U 600/1000V

Notes:
1.    Strande|d conductor only.
2.    Clauses 8 (Bending) and 9.1 & 9.2 (Impact) cannot be conducted due to the cable having only one core.
3.    These cables also met category C,W,Z when tested for voltage rating 600/1000V which is not recognised by BS 6387.
4.    Where a single cable is fitted in a conduit, only phase to earth voltage was applied.
5.    To satisfy the requirement of BS 6387, testing for C, W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element.
6.    To satisfy the requirement of BS 6387, testing for W & Z categories was conducted using a 20mm stainless steel conduit as the other metallic element.
7.    To satisfy the requirement of BS 6387, testing for C category was conducted using a 38mm stainless steel conduit as the other metallic element.
8.    Only Clause 10 of BS 6387 was conducted.
9.    The BETAflam FR-MI 110 Cable Single Core SI cables met the requirements of IEC 60331-21: 1999 when tested at a temperature of 950oC and at a voltage rating of 600V.

 


 

To read the Red Book section introduction click here.

 