Search by Certificate Number

Schneider Electric Fire & Security Oy

Sokerilinnantie 11C
02600
Espoo
Finland

Tel: +358 10 446 511 • Fax: +358 10 446 5103
Email: FI-FireSecurity-Info@schneider-electric.com • Web: www.schneider-electric.com


Certificate No 199p to EN54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003
Certificate No 199t to LPS 1279 - 1.0: 2006, EN 54-5: 2000 + A1: 2002, EN 54-7: 2000 + A1: 2002 & CEA 4021: 2003
Certificate No 010aq-(cl-2) to LPS 1274: 2005 EN 54-5: 2000 + A1: 2002 LPS 1265: 2004

Certificate No 010h to EN 54-7:2000 + A1:2002 + A2:2006, EN 54-5:2000 + A1:2002, CEA 4021:2003
Certificate No 010bb-(cl-2) to EN 54-5:2000 + A1:2002, EN 54-7:2000 + A1:2002 + A2:2006, EN 54-17:2005 & CEA 4021:2003


Multi Criteria Detectors

Product Description LPCB
Ref. No.
ED2351TEM

Conventional optical/thermal smoke & heat detector

(B401, B401DG, B401R, B401SD and B401RSD bases)

Note:

1. Meets the requirements of EN 54-5: 2000 at class A1R and EN 54-7: 2000 at High, Medium and Low.

199p/03
ESMI2251CTLE

Analogue addressable multi-criteria fire detector and incorporating CO, photoelectric, thermal and IR sensors (B501, B501AP, B501DG and B524IEFT-1 bases)

Note: Certified at the following settings: -

Normal Mode:

Alarm Levels 1 to 5 (Multi-criteria) EN54-5 Class A1R, EN54-7, LPS1279 and CEA 4021

Alarm Level 6 (Heat Only Mode): EN54-5 Class A1R

Nuisance Environment Applications:

Application 0,        Alarm Level 4         EN54-7, LPS1279 & CEA 4021

Application 1,        Alarm Level 5        EN54-5 Class A1R, EN54-7 & CEA 4021

Application 2,        Alarm Level 4 or 5        EN54-5 Class A1R, EN54-7 & CEA 4021

Application 3,        Alarm Level 5        EN54-5 Class A1R, EN54-7 & CEA 4021

Application 4,        Alarm Level 5        EN54-5 Class A1R, EN54-7 & CEA 4021

Application 5,        Alarm Level 5        EN54-7 & CEA 4021

Application 6,        Alarm Level 5        EN54-5 Class A1R, EN54-7 & CEA 4021

199t/01
EDI-30

ESMI Intellia Multisensor Smoke Detector

(EBI-10 and EBI-12 bases)

Note:

1. Certified at the following settings:

Mode 1 - High sensitivity smoke detector with standard heat enhancement

Mode 2 - Smoke detection only

Mode 3 - Medium sensitivity smoke detector with standard heat enhancement

Mode 4 - Low sensitivity smoke detector with high heat enhancement

Mode 5 - Class A1 heat detector

Also approved in conventional alarm modes 1, 2, 3, 4 and 5

2. Approved with Apollo Discovery, XP95, and S90 digital communication protocols that have been configured for the Discovery multisensor detector in accordance with manufacturer's instructions.

010h/01
EDE223-I

ESMI Essentia Smoke/Heat Detector with Multi-Criteria Detector (EBE200-N base)

Certified at the following settings:

Mode 1: High sensitivity smoke detector with high heat enhancement

Mode 2: Standard smoke sensitivity only

Mode 3: Medium sensitivity smoke detector with medium heat enhancement

Mode 4: Low sensitivity smoke detector with high heat enhancement

Mode 5: Class A1R heat detector

010bb/01

 

Bases:
B401 standard base
B401DG deep base
B401R standard base with 470 ohm resistor
B401SD standard base with schottky diode
B401RSD standard base with 470 ohm resistor and schottky diode
B501 standard analogue detector base
B501AP intelligent detector base
B501DG Deep detector base
B524IEFT Short circuit isolator base
B524HTR Heater base
B524RTE Latching relay base
EBI-10 Standard Intelligent Mounting Base
EBI-12 ESMI Intellia Mounting Base
EBE200-N ESMI Essentia Xpert 8 Mounting Base
 

 


 

To read the Red Book section introduction click here.

 

< back to results page

< back to search page