Nitin Fire Protection Industries Ltd (NITIE)
501 Delta
Technology Street
Hirandani Gardens, Powai
Mumbai 400 076
India
Tel: +91 22 40457000
•
Fax: +91 22 66920910
Email: systems@nitinfire.com
•
Web: www.nitinfire.com
Certificate No 855d to LPS 1230
Product | Risk | Design Concentration | Comments | LPCB Ref. No. |
---|---|---|---|---|
Nitin1230 | Class A Standard (Solid fires e.g. paper, wood, plastics) |
5.3% |
Design concentration includes 30% safety factor |
855d/02 |
See below for all products listed in this group including notes.
Product | Risk | Design Concentration | Comments | LPCB Ref. No. |
---|---|---|---|---|
Nitin1230 | Class A Standard (Solid fires e.g. paper, wood, plastics) |
5.3% |
Design concentration includes 30% safety factor |
855d/02 |
Nitin1230 | Class A Cables (Solid fires risks including cables) |
5.5% |
Confirmation that 'minimum safety factor' is adequate |
855d/02 |
Nitin1230 | Class B (Liquid Fires e.g.heptane) |
6.5% |
Design concentration includes 30% safety factor |
855d/02 |
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
To read the Red Book section introduction click here.